LIBRARY
Examples.HeatExchanger.WaterToWaterCounterFlow ​
Transient counterflow heat exchanger with hot liquid water transferring heat to cold liquid water.
All numerical operating conditions, geometry, initialization values, and the concrete medium selection are confined to this example. Both streams flow in their positive design directions; BasicHX reverses the stream-2 thermal segment connections to represent counterflow heat exchange.
Usage ​
FluidComponents.Examples.HeatExchanger.WaterToWaterCounterFlow(T_hot_in=360, T_cold_in=300, T_hot_start=330, T_cold_start=320, T_wall_start=325, m_flow_hot=0.2, m_flow_cold=0.2, p_outlet=100000, p_inlet_start=101000)
Parameters: ​
| Name | Description | Units | Default value |
|---|---|---|---|
medium_data | – | MediaCompon...WaterData() | |
nNodes | – | 4 | |
T_hot_in | K | 360 | |
T_cold_in | K | 300 | |
T_hot_start | K | 330 | |
T_cold_start | K | 320 | |
T_wall_start | K | 325 | |
m_flow_hot | kg/s | 0.2 | |
m_flow_cold | kg/s | 0.2 | |
p_outlet | Pa | 100000 | |
p_inlet_start | Pa | 101000 |
Variables ​
| Name | Description | Units |
|---|---|---|
T_hot_out | K | |
T_cold_out | K | |
T_wall_mean | K | |
Q_hot | W | |
Q_cold | W |
Behavior ​
Source ​
dyad
"""
Transient counterflow heat exchanger with hot liquid water transferring heat to
cold liquid water.
All numerical operating conditions, geometry, initialization values, and the
concrete medium selection are confined to this example. Both streams flow in
their positive design directions; BasicHX reverses the stream-2 thermal segment
connections to represent counterflow heat exchange.
"""
component WaterToWaterCounterFlow
"Distributed counterflow heat exchanger."
heat_exchanger = FluidComponents.Examples.HeatExchanger.BaseClasses.BasicHX(medium_data_1 = medium_data, medium_data_2 = medium_data, nNodes = nNodes, modelStructure_1 = FluidComponents.Types.ModelStructure.av_b(), modelStructure_2 = FluidComponents.Types.ModelStructure.a_vb(), allowFlowReversal = true, energyDynamics = FluidComponents.Types.Dynamics.FixedInitial(), massDynamics = FluidComponents.Types.Dynamics.SteadyState(), momentumDynamics = FluidComponents.Types.Dynamics.SteadyState(), use_T_start = true, length = 5, crossArea_1 = 4.5e-4, crossArea_2 = 4.5e-4, perimeter_1 = 0.075, perimeter_2 = 0.075, area_h_1 = 0.375, area_h_2 = 0.375, nParallel_1 = 1, nParallel_2 = 1, height_ab_1 = 0, height_ab_2 = 0, roughness_1 = 2.5e-5, roughness_2 = 2.5e-5, dp_nominal_1 = 1000, dp_nominal_2 = 1000, m_flow_nominal_1 = m_flow_hot, m_flow_nominal_2 = m_flow_cold, alpha0_1 = 1000, alpha0_2 = 1000, k_ambient_1 = 0, k_ambient_2 = 0, T_ambient_1 = 300, T_ambient_2 = 300, s_wall = 0.002, k_wall = 15, c_wall = 500, rho_wall = 7800, Twall_start = T_wall_start, dT = 0, p_a_start_1 = p_inlet_start, p_b_start_1 = p_outlet, p_a_start_2 = p_inlet_start, p_b_start_2 = p_outlet, T_start_1 = T_hot_start, T_start_2 = T_cold_start, h_start_1 = 4184 * (T_hot_start - 273.15), h_start_2 = 4184 * (T_cold_start - 273.15), m_flow_start_1 = m_flow_hot, m_flow_start_2 = m_flow_cold) {
"Dyad": {"placement": {"diagram": {"x1": 155, "x2": 255, "y1": 139, "y2": 239}}}
}
"Prescribed hot-water inlet."
hot_source = FluidComponents.Sources.MassFlowSource_T(medium_data = medium_data, nPorts = 1, use_m_flow_in = false, m_flow = m_flow_hot, T = T_hot_in) {
"Dyad": {"placement": {"diagram": {"x1": -100, "x2": 0, "y1": 260, "y2": 360}}}
}
"Fixed-pressure hot-water outlet."
hot_sink = FluidComponents.Sources.Boundary_pT(medium_data = medium_data, nPorts = 1, p = p_outlet, T = T_hot_in) {
"Dyad": {"placement": {"diagram": {"x1": 670, "x2": 570, "y1": 10, "y2": 110}}}
}
"Prescribed cold-water inlet."
cold_source = FluidComponents.Sources.MassFlowSource_T(medium_data = medium_data, nPorts = 1, use_m_flow_in = false, m_flow = m_flow_cold, T = T_cold_in) {
"Dyad": {"placement": {"diagram": {"x1": 650, "x2": 550, "y1": 340, "y2": 440}}}
}
"Fixed-pressure cold-water outlet."
cold_sink = FluidComponents.Sources.Boundary_pT(medium_data = medium_data, nPorts = 1, p = p_outlet, T = T_cold_in) {"Dyad": {"placement": {"diagram": {"x1": -70, "x2": 30, "y1": 0, "y2": 100}}}}
# Concrete medium selected when the example is constructed [-]
structural parameter medium_data::MediaComponents.Interfaces.AbstractPartialMediumData = MediaComponents.Water.ConstantPropertyLiquidWaterData()
# Number of axial fluid and wall segments [-]
structural parameter nNodes::Integer(min = 1) = 4
# Hot-stream inlet temperature [K]
parameter T_hot_in::Temperature = 360
# Cold-stream inlet temperature [K]
parameter T_cold_in::Temperature = 300
# Hot-stream initial temperature [K]
parameter T_hot_start::Temperature = 330
# Cold-stream initial temperature [K]
parameter T_cold_start::Temperature = 320
# Wall initial temperature [K]
parameter T_wall_start::Temperature = 325
# Mass flow rate through the hot stream [kg/s]
parameter m_flow_hot::MediaComponents.Types.MassFlowRate = 0.2
# Mass flow rate through the cold stream [kg/s]
parameter m_flow_cold::MediaComponents.Types.MassFlowRate = 0.2
# Outlet pressure of each stream [Pa]
parameter p_outlet::MediaComponents.Types.AbsolutePressure = 100000
# Nominal inlet pressure used for initialization [Pa]
parameter p_inlet_start::MediaComponents.Types.AbsolutePressure = 101000
# Hot-stream outlet temperature [K]
variable T_hot_out::Temperature
# Cold-stream outlet temperature [K]
variable T_cold_out::Temperature
# Mean wall temperature [K]
variable T_wall_mean::Temperature
# Total heat flow into the hot stream [W]
variable Q_hot::HeatFlowRate
# Total heat flow into the cold stream [W]
variable Q_cold::HeatFlowRate
relations
connect(hot_source.ports[1], heat_exchanger.port_a1) {
"Dyad": {
"edges": [{"S": 1, "M": [{"x": 20, "y": 310}, {"x": 20, "y": 190}], "E": 2}],
"path": {}
}
}
connect(heat_exchanger.port_b1, hot_sink.ports[1]) {
"Dyad": {
"edges": [{"S": 1, "M": [{"x": 402.5, "y": 190}, {"x": 402.5, "y": 60}], "E": 2}],
"path": {}
}
}
connect(cold_source.ports[1], heat_exchanger.port_a2) {
"Dyad": {
"edges": [{"S": 1, "M": [{"x": 330, "y": 390}, {"x": 330, "y": 212}], "E": 2}],
"path": {}
}
}
connect(heat_exchanger.port_b2, cold_sink.ports[1]) {
"Dyad": {
"edges": [{"S": 1, "M": [{"x": 140, "y": 166}, {"x": 140, "y": 50}], "E": 2}],
"path": {}
}
}
T_hot_out = heat_exchanger.pipe_1.mediums[nNodes].T
T_cold_out = heat_exchanger.pipe_2.mediums[nNodes].T
T_wall_mean = sum(heat_exchanger.wall.T) / nNodes
Q_hot = heat_exchanger.Q_flow_1
Q_cold = heat_exchanger.Q_flow_2
endFlattened Source
dyad
"""
Transient counterflow heat exchanger with hot liquid water transferring heat to
cold liquid water.
All numerical operating conditions, geometry, initialization values, and the
concrete medium selection are confined to this example. Both streams flow in
their positive design directions; BasicHX reverses the stream-2 thermal segment
connections to represent counterflow heat exchange.
"""
component WaterToWaterCounterFlow
"Distributed counterflow heat exchanger."
heat_exchanger = FluidComponents.Examples.HeatExchanger.BaseClasses.BasicHX(medium_data_1 = medium_data, medium_data_2 = medium_data, nNodes = nNodes, modelStructure_1 = FluidComponents.Types.ModelStructure.av_b(), modelStructure_2 = FluidComponents.Types.ModelStructure.a_vb(), allowFlowReversal = true, energyDynamics = FluidComponents.Types.Dynamics.FixedInitial(), massDynamics = FluidComponents.Types.Dynamics.SteadyState(), momentumDynamics = FluidComponents.Types.Dynamics.SteadyState(), use_T_start = true, length = 5, crossArea_1 = 4.5e-4, crossArea_2 = 4.5e-4, perimeter_1 = 0.075, perimeter_2 = 0.075, area_h_1 = 0.375, area_h_2 = 0.375, nParallel_1 = 1, nParallel_2 = 1, height_ab_1 = 0, height_ab_2 = 0, roughness_1 = 2.5e-5, roughness_2 = 2.5e-5, dp_nominal_1 = 1000, dp_nominal_2 = 1000, m_flow_nominal_1 = m_flow_hot, m_flow_nominal_2 = m_flow_cold, alpha0_1 = 1000, alpha0_2 = 1000, k_ambient_1 = 0, k_ambient_2 = 0, T_ambient_1 = 300, T_ambient_2 = 300, s_wall = 0.002, k_wall = 15, c_wall = 500, rho_wall = 7800, Twall_start = T_wall_start, dT = 0, p_a_start_1 = p_inlet_start, p_b_start_1 = p_outlet, p_a_start_2 = p_inlet_start, p_b_start_2 = p_outlet, T_start_1 = T_hot_start, T_start_2 = T_cold_start, h_start_1 = 4184 * (T_hot_start - 273.15), h_start_2 = 4184 * (T_cold_start - 273.15), m_flow_start_1 = m_flow_hot, m_flow_start_2 = m_flow_cold) {
"Dyad": {"placement": {"diagram": {"x1": 155, "x2": 255, "y1": 139, "y2": 239}}}
}
"Prescribed hot-water inlet."
hot_source = FluidComponents.Sources.MassFlowSource_T(medium_data = medium_data, nPorts = 1, use_m_flow_in = false, m_flow = m_flow_hot, T = T_hot_in) {
"Dyad": {"placement": {"diagram": {"x1": -100, "x2": 0, "y1": 260, "y2": 360}}}
}
"Fixed-pressure hot-water outlet."
hot_sink = FluidComponents.Sources.Boundary_pT(medium_data = medium_data, nPorts = 1, p = p_outlet, T = T_hot_in) {
"Dyad": {"placement": {"diagram": {"x1": 670, "x2": 570, "y1": 10, "y2": 110}}}
}
"Prescribed cold-water inlet."
cold_source = FluidComponents.Sources.MassFlowSource_T(medium_data = medium_data, nPorts = 1, use_m_flow_in = false, m_flow = m_flow_cold, T = T_cold_in) {
"Dyad": {"placement": {"diagram": {"x1": 650, "x2": 550, "y1": 340, "y2": 440}}}
}
"Fixed-pressure cold-water outlet."
cold_sink = FluidComponents.Sources.Boundary_pT(medium_data = medium_data, nPorts = 1, p = p_outlet, T = T_cold_in) {"Dyad": {"placement": {"diagram": {"x1": -70, "x2": 30, "y1": 0, "y2": 100}}}}
# Concrete medium selected when the example is constructed [-]
structural parameter medium_data::MediaComponents.Interfaces.AbstractPartialMediumData = MediaComponents.Water.ConstantPropertyLiquidWaterData()
# Number of axial fluid and wall segments [-]
structural parameter nNodes::Integer(min = 1) = 4
# Hot-stream inlet temperature [K]
parameter T_hot_in::Temperature = 360
# Cold-stream inlet temperature [K]
parameter T_cold_in::Temperature = 300
# Hot-stream initial temperature [K]
parameter T_hot_start::Temperature = 330
# Cold-stream initial temperature [K]
parameter T_cold_start::Temperature = 320
# Wall initial temperature [K]
parameter T_wall_start::Temperature = 325
# Mass flow rate through the hot stream [kg/s]
parameter m_flow_hot::MediaComponents.Types.MassFlowRate = 0.2
# Mass flow rate through the cold stream [kg/s]
parameter m_flow_cold::MediaComponents.Types.MassFlowRate = 0.2
# Outlet pressure of each stream [Pa]
parameter p_outlet::MediaComponents.Types.AbsolutePressure = 100000
# Nominal inlet pressure used for initialization [Pa]
parameter p_inlet_start::MediaComponents.Types.AbsolutePressure = 101000
# Hot-stream outlet temperature [K]
variable T_hot_out::Temperature
# Cold-stream outlet temperature [K]
variable T_cold_out::Temperature
# Mean wall temperature [K]
variable T_wall_mean::Temperature
# Total heat flow into the hot stream [W]
variable Q_hot::HeatFlowRate
# Total heat flow into the cold stream [W]
variable Q_cold::HeatFlowRate
relations
connect(hot_source.ports[1], heat_exchanger.port_a1) {
"Dyad": {
"edges": [{"S": 1, "M": [{"x": 20, "y": 310}, {"x": 20, "y": 190}], "E": 2}],
"path": {}
}
}
connect(heat_exchanger.port_b1, hot_sink.ports[1]) {
"Dyad": {
"edges": [{"S": 1, "M": [{"x": 402.5, "y": 190}, {"x": 402.5, "y": 60}], "E": 2}],
"path": {}
}
}
connect(cold_source.ports[1], heat_exchanger.port_a2) {
"Dyad": {
"edges": [{"S": 1, "M": [{"x": 330, "y": 390}, {"x": 330, "y": 212}], "E": 2}],
"path": {}
}
}
connect(heat_exchanger.port_b2, cold_sink.ports[1]) {
"Dyad": {
"edges": [{"S": 1, "M": [{"x": 140, "y": 166}, {"x": 140, "y": 50}], "E": 2}],
"path": {}
}
}
T_hot_out = heat_exchanger.pipe_1.mediums[nNodes].T
T_cold_out = heat_exchanger.pipe_2.mediums[nNodes].T
T_wall_mean = sum(heat_exchanger.wall.T) / nNodes
Q_hot = heat_exchanger.Q_flow_1
Q_cold = heat_exchanger.Q_flow_2
metadata {}
endTest Cases ​
No test cases defined.
Related ​
Examples
Experiments
Analyses