Examples.HVAC.HVACPlant ​
Linear thermal model of a house heated by a heat pump through floor heating, the model of the DyadControlSystems HVAC tutorial (https://help.juliahub.com/dyad/DyadControlSystems.jl/stable/examples/hvac/). Four lumped temperatures — wall, indoor air, floor and circulating water — exchange heat with time constants in hours; the heat pump's compressor power level power (kW, 0–4) heats the water and the outdoor temperature Text acts on the wall. Time is in hours.
The output y is the indoor temperature. The model is linear, so its linearization is exact; HVACClosedLoop gives the plant itself to its MPC as the prediction model.
Usage ​
MPCComponents.Examples.HVAC.HVACPlant(tau_wall_ext=48.0, tau_wall_int=18.0, tau_int_floor=3.6, tau_water_floor=6.0, input_gain=0.1666, T0=18.0)
Parameters: ​
| Name | Description | Units | Default value |
|---|---|---|---|
tau_wall_ext | Wall–outdoor time constant [h] | – | 48.0 |
tau_wall_int | Wall–indoor air time constant [h] | – | 18.0 |
tau_int_floor | Indoor air–floor time constant [h] | – | 3.6 |
tau_water_floor | Water–floor time constant [h] | – | 6.0 |
input_gain | Heating gain of the compressor power [°C/(h kW)], COP 4.9 × 0.034 | – | 0.1666 |
T0 | Initial temperature of all four lumps [°C] | – | 18.0 |
Connectors ​
power- This connector represents a real signal as an input to a component (RealInput)Text- This connector represents a real signal as an input to a component (RealInput)y- This connector represents a real signal as an output from a component (RealOutput)
Variables ​
| Name | Description | Units |
|---|---|---|
Twall | Wall temperature [°C] | – |
Tint | Indoor air temperature [°C] | – |
Tfloor | Floor temperature [°C] | – |
Twater | Circulating water temperature [°C] | – |
Behavior ​
Behavior of this component cannot be rendered because it includes path variables.
Source ​
"""
Linear thermal model of a house heated by a heat pump through floor heating, the model of the
DyadControlSystems HVAC tutorial (https://help.juliahub.com/dyad/DyadControlSystems.jl/stable/examples/hvac/).
Four lumped temperatures — wall, indoor air, floor and circulating water — exchange heat with time
constants in hours; the heat pump's compressor power level `power` (kW, 0–4) heats the water and the
outdoor temperature `Text` acts on the wall. Time is in hours.
```math
\\begin{aligned}
\\dot T_{wall} &= (T_{ext} - T_{wall})/\\tau_{wall,ext} + (T_{int} - T_{wall})/\\tau_{wall,int} \\\\
\\dot T_{int} &= (T_{wall} - T_{int})/\\tau_{wall,int} + (T_{floor} - T_{int})/\\tau_{int,floor} \\\\
\\dot T_{floor} &= (T_{int} - T_{floor})/\\tau_{int,floor} + (T_{water} - T_{floor})/\\tau_{water,floor} \\\\
\\dot T_{water} &= (T_{floor} - T_{water})/\\tau_{water,floor} + k_{in}\\, power
\\end{aligned}
```
The output `y` is the indoor temperature. The model is linear, so its linearization is exact;
`HVACClosedLoop` gives the plant itself to its MPC as the prediction model.
"""
component HVACPlant
"Heat-pump compressor power level [kW]"
power = RealInput() {
"Dyad": {
"placement": {
"diagram": {"iconName": "default", "x1": -100, "y1": 350, "x2": 0, "y2": 450, "rot": 0}
},
"tags": []
}
}
"Outdoor temperature [°C]"
Text = RealInput() {
"Dyad": {
"placement": {
"diagram": {"iconName": "default", "x1": -100, "y1": 550, "x2": 0, "y2": 650, "rot": 0}
},
"tags": []
}
}
"Indoor air temperature [°C]"
y = RealOutput() {
"Dyad": {
"placement": {
"diagram": {"iconName": "default", "x1": 1000, "y1": 450, "x2": 1100, "y2": 550, "rot": 0}
},
"tags": []
}
}
"Wall–outdoor time constant [h]"
parameter tau_wall_ext::Real = 48.0
"Wall–indoor air time constant [h]"
parameter tau_wall_int::Real = 18.0
"Indoor air–floor time constant [h]"
parameter tau_int_floor::Real = 3.6
"Water–floor time constant [h]"
parameter tau_water_floor::Real = 6.0
"Heating gain of the compressor power [°C/(h kW)], COP 4.9 × 0.034"
parameter input_gain::Real = 0.1666
"Initial temperature of all four lumps [°C]"
parameter T0::Real = 18.0
"Wall temperature [°C]"
variable Twall::Real(initial = T0)
"Indoor air temperature [°C]"
variable Tint::Real(initial = T0)
"Floor temperature [°C]"
variable Tfloor::Real(initial = T0)
"Circulating water temperature [°C]"
variable Twater::Real(initial = T0)
relations
der(Twall) = (Text - Twall) / tau_wall_ext + (Tint - Twall) / tau_wall_int
der(Tint) = (Twall - Tint) / tau_wall_int + (Tfloor - Tint) / tau_int_floor
der(Tfloor) = (Tint - Tfloor) / tau_int_floor + (Twater - Tfloor) / tau_water_floor
der(Twater) = (Tfloor - Twater) / tau_water_floor + input_gain * power
y = Tint
metadata {
"Dyad": {
"icons": {"default": "dyad://MPCComponents/HVACPlant.svg"},
"doc": {"behavior": false}
}
}
endFlattened Source
"""
Linear thermal model of a house heated by a heat pump through floor heating, the model of the
DyadControlSystems HVAC tutorial (https://help.juliahub.com/dyad/DyadControlSystems.jl/stable/examples/hvac/).
Four lumped temperatures — wall, indoor air, floor and circulating water — exchange heat with time
constants in hours; the heat pump's compressor power level `power` (kW, 0–4) heats the water and the
outdoor temperature `Text` acts on the wall. Time is in hours.
```math
\\begin{aligned}
\\dot T_{wall} &= (T_{ext} - T_{wall})/\\tau_{wall,ext} + (T_{int} - T_{wall})/\\tau_{wall,int} \\\\
\\dot T_{int} &= (T_{wall} - T_{int})/\\tau_{wall,int} + (T_{floor} - T_{int})/\\tau_{int,floor} \\\\
\\dot T_{floor} &= (T_{int} - T_{floor})/\\tau_{int,floor} + (T_{water} - T_{floor})/\\tau_{water,floor} \\\\
\\dot T_{water} &= (T_{floor} - T_{water})/\\tau_{water,floor} + k_{in}\\, power
\\end{aligned}
```
The output `y` is the indoor temperature. The model is linear, so its linearization is exact;
`HVACClosedLoop` gives the plant itself to its MPC as the prediction model.
"""
component HVACPlant
"Heat-pump compressor power level [kW]"
power = RealInput() {
"Dyad": {
"placement": {
"diagram": {"iconName": "default", "x1": -100, "y1": 350, "x2": 0, "y2": 450, "rot": 0}
},
"tags": []
}
}
"Outdoor temperature [°C]"
Text = RealInput() {
"Dyad": {
"placement": {
"diagram": {"iconName": "default", "x1": -100, "y1": 550, "x2": 0, "y2": 650, "rot": 0}
},
"tags": []
}
}
"Indoor air temperature [°C]"
y = RealOutput() {
"Dyad": {
"placement": {
"diagram": {"iconName": "default", "x1": 1000, "y1": 450, "x2": 1100, "y2": 550, "rot": 0}
},
"tags": []
}
}
"Wall–outdoor time constant [h]"
parameter tau_wall_ext::Real = 48.0
"Wall–indoor air time constant [h]"
parameter tau_wall_int::Real = 18.0
"Indoor air–floor time constant [h]"
parameter tau_int_floor::Real = 3.6
"Water–floor time constant [h]"
parameter tau_water_floor::Real = 6.0
"Heating gain of the compressor power [°C/(h kW)], COP 4.9 × 0.034"
parameter input_gain::Real = 0.1666
"Initial temperature of all four lumps [°C]"
parameter T0::Real = 18.0
"Wall temperature [°C]"
variable Twall::Real(initial = T0)
"Indoor air temperature [°C]"
variable Tint::Real(initial = T0)
"Floor temperature [°C]"
variable Tfloor::Real(initial = T0)
"Circulating water temperature [°C]"
variable Twater::Real(initial = T0)
relations
der(Twall) = (Text - Twall) / tau_wall_ext + (Tint - Twall) / tau_wall_int
der(Tint) = (Twall - Tint) / tau_wall_int + (Tfloor - Tint) / tau_int_floor
der(Tfloor) = (Tint - Tfloor) / tau_int_floor + (Twater - Tfloor) / tau_water_floor
der(Twater) = (Tfloor - Twater) / tau_water_floor + input_gain * power
y = Tint
metadata {
"Dyad": {
"icons": {"default": "dyad://MPCComponents/HVACPlant.svg"},
"doc": {"behavior": false}
}
}
endTest Cases ​
No test cases defined.