Components.Partial.PartialHEXCrossflow

Partial base class for a moist-air cross-flow heat-exchanger element.

Defines the moist-air ports, the wall heat-port array, mass/energy/water-vapor balances and pressure-drop equation for an N-cell air stream. Extending components must declare N (the number of control volumes), supply the air-side heat-transfer coefficient htc[i] (typically via an initial binding to htc_nominal), the mass-transfer-driven condensation closure (mcond_flow[i]) and the fin efficiency eta_fin[i], plus the pressure-drop relation that defines p_loss. port_a is the upstream air port and port_b the downstream air port (m_flow > 0 means air enters port_a). medium_data must be a moist-air medium.

Usage

HVACComponents.Components.Partial.PartialHEXCrossflow(htc_nominal, CF_MassTransfer, CF_HeatTransfer, htc=missing, p_in_start, p_out_start, p_loss_start, m_air_flow_start, T_in_start, T_out_start, Xi_in_start, Xi_out_start, Q_start, eta_fin_start, h_in_start, h_out_start, mcond_flow_start, d_mean_start, Q_water_start, cp_mean_start, medium_data)

Parameters:

NameDescriptionUnitsDefault value
NNumber of air-side control volumes1
N_Plus_1Number of cell faces (= N + 1)N + 1
htc_nominalNominal air-side heat-transfer coefficient [W/(m^2.K)]
CF_MassTransferCorrection factor on the Lewis-analogy mass-transfer coefficient [-]
CF_HeatTransferCorrection factor on the air-side heat-transfer coefficient [-]
p_in_startInitial air inlet pressure [Pa]Pa
p_out_startInitial air outlet pressure [Pa]Pa
p_loss_startInitial air-side pressure drop [Pa]Pa
m_air_flow_startInitial air mass flow rate [kg/s]kg/s
T_in_startInitial air inlet temperature [K]K
T_out_startInitial air outlet temperature [K]K
Xi_in_startInitial air inlet water-vapor mass fraction [-]
Xi_out_startInitial air outlet water-vapor mass fraction [-]
Q_startInitial air-side heat flow per element [W]W
eta_fin_startInitial fin efficiency [-]
h_in_startInitial air inlet specific enthalpy [J/kg]J/kg
h_out_startInitial air outlet specific enthalpy [J/kg]J/kg
mcond_flow_startInitial condensate mass flow [kg/s]kg/s
d_mean_startInitial mean air density [kg/m^3]
Q_water_startInitial heat flow carried by condensate [W]W
cp_mean_startInitial mean specific heat capacity of moist air [J/(kg.K)]
medium_dataMoist-air medium properties

Connectors

Variables

NameDescriptionUnits
pAir-side pressure used internally (= medium_inflow.p = port_a.p) [Pa]Pa
TAir temperature at each face [K] (length N+1)K
H_flowEnthalpy flow at each face [W] (length N+1)
mdotDry-and-vapor mass flow at each face [kg/s] (length N+1)kg/s
mXi_flowWater-vapor mass flow at each face [kg/s] (length N+1)
Q_flowSensible-plus-latent heat flow into each cell [W] (length N)W
mcond_flowCondensate mass flow leaving each cell [kg/s] (length N)
p_lossAir-side pressure drop port_a - port_b [Pa]Pa
d_meanMean air density used in mass-transfer scaling [kg/m^3]
Q_waterHeat flow carried out with the condensate [W]W
cp_meanMean specific heat capacity of moist air [J/(kg.K)]
T_inAir inlet temperature [K] (alias for medium_inflow.T at port_a)K
T_outAir outlet temperature [K] (alias for medium_outflow.T at port_b)K
eta_finFin efficiency per cell [-] (length N); extender supplies